      Daylight Comfort Performance of a Vertical Fin Shading System: Annual Simulation and Experimental Testing of a Prototype

      Buildings
      MDPI AG

      Read this article at

      Bookmark
          There is no author summary for this article yet. Authors can add summaries to their articles on ScienceOpen to make them more accessible to a non-specialist audience.

          Abstract

          This study aims to develop and evaluate a vertically rotated fin shading system for an energy-efficient, user-friendly office space. The system was designed to protect a 4 × 8 m office room with a south-facing facade from excessive solar radiation and glare. The shading system was modelled and simulated using Rhino/Ladybug 1.6.0 software with Radiance engine, based on real-weather data (*.epw file) for Wrocław, Poland at 51° lat. The simulation calculated the useful daylight illuminance (UDI) for 300–3000 lux and the daylight glare probability (DGP) for ten static and four kinetic variants of the system. The optimal angle of the fin rotation for the static variant was found to be α = 40°. The kinetic variants were activated when the work plane illuminance exceeded 3000 lux, as detected by an internal sensor “A”. The simulation results show that the kinetic system improved the daylight uniformity in the office room, achieving UDI300–3000 values above 80% for more than 40% of the room area. A prototype of the system in a 1:20 scale was built and tested on a testbed at Wrocław University of Science and Technology, using TESTO THL 160 data loggers. The measurements were conducted for a week in early November 2023, and three clear days were selected for analysis. The measurement results indicate that the low solar altitude on clear days causes high illuminance peaks (15–18 Klux) and significant contrast in the room, leading to unsatisfactory DGP values consistent with the simulation outcomes. Therefore, the study concludes that the proposed system may need an additional shading device to prevent glare during periods of low solar altitudes.

          Related collections

          Most cited references49

          • Record: found
          • Abstract: not found
          • Article: not found

          Evaluation methods and development of a new glare prediction model for daylight environments with the use of CCD cameras

            Bookmark
            • Record: found
            • Abstract: not found
            • Article: not found

            Validation of dynamic RADIANCE-based daylight simulations for a test office with external blinds

              Bookmark
              • Record: found
              • Abstract: not found
              • Article: not found

              Useful daylight illuminance: a new paradigm for assessing daylight in buildings

                Bookmark

                Author and article information

                Contributors
                (View ORCID Profile)
                Journal
                BUILCO
                Buildings
                Buildings
                MDPI AG
                2075-5309
                March 2024
                February 21 2024
                : 14
                : 3
                : 571
                Article
                10.3390/buildings14030571
                624f06e6-4cf3-41ca-b9d5-2a7bf40cdc14
                © 2024

                https://creativecommons.org/licenses/by/4.0/

                History

                Comments

                Comment on this article