      Accuracy Improvement of Transformer Faults Diagnostic Based on DGA Data Using SVM-BA Classifier

      , , , ,
      Energies
      MDPI AG

      Read this article at

      Bookmark
          There is no author summary for this article yet. Authors can add summaries to their articles on ScienceOpen to make them more accessible to a non-specialist audience.

          Abstract

          The main objective of the current work was to enhance the transformer fault diagnostic accuracy based on dissolved gas analysis (DGA) data with a proposed coupled system of support vector machine (SVM)-bat algorithm (BA) and Gaussian classifiers. Six electrical and thermal fault classes were categorized based on the IEC and IEEE standard rules. The concentration of five main combustible gases (hydrogen, methane, ethane, ethylene, and acetylene) was utilized as an input vector of the two classifiers. Two types of input vectors have been tested; the first input type considered the five gases in ppm, and the second input type considered the gases introduced in the percentage of the sum of the five gases. An extensive database of 481 had been used for training and testing phases (321 data samples for training and 160 data samples for testing). The SVM model conditioning parameter “λ” and penalty margin parameter “C” were adjusted through the bat algorithm to develop a maximum accuracy rate. The SVM-BA and Gaussian classifiers’ accuracy was evaluated and compared with several DGA techniques in the literature.

          Related collections

          Most cited references19

          • Record: found
          • Abstract: not found
          • Article: not found

          A BA-based algorithm for parameter optimization of Support Vector Machine

            Bookmark
            • Record: found
            • Abstract: not found
            • Article: not found

            A new approach of DGA interpretation technique for transformer fault diagnosis

              Bookmark
              • Record: found
              • Abstract: not found
              • Article: not found

              The duval pentagon-a new complementary tool for the interpretation of dissolved gas analysis in transformers

              (2014)
                Bookmark

                Author and article information

                Contributors
                (View ORCID Profile)
                (View ORCID Profile)
                (View ORCID Profile)
                (View ORCID Profile)
                Journal
                ENERGA
                Energies
                Energies
                MDPI AG
                1996-1073
                May 2021
                May 20 2021
                : 14
                : 10
                : 2970
                Article
                10.3390/en14102970
                a9e64828-24ad-4334-8e5d-1caea4d8748a
                © 2021

                https://creativecommons.org/licenses/by/4.0/

                History

                Comments

                Comment on this article